Know what a plan reviewer looks for before you submit.
These are the 36 items our plan check reads a house set against, each with the code section or local rule behind it. You can run it on a set you already have, and a house drawn here comes with its own code review.
A permit follows the code in force on the day it is filed: the FBC Residential, 8th Edition (2023) today, and the FBC Residential, 9th Edition (2026) from December 31, 2026. Where the new edition changes an item, both are shown.
General
- G1
Cover with sheet index, project address, owner or builder, and scope of work
Local submittal checklists
- G2
Code edition stated: Florida Building Code, Residential, 8th Edition (2023), which governs permit applications filed before the 9th Edition takes effect, planned for December 31, 2026
From December 31, 2026: Code edition stated: Florida Building Code, Residential, 9th Edition (2026), which governs permit applications filed on or after its effective date, planned for December 31, 2026
FBC-R R101, local checklists
- G3
Designer of record: name, Florida license number, address and phone; signed and sealed (digital seal) on the sheets
F.S. 471.025, 481.221; Hillsborough HC-03
- G4
Structural design criteria: Vult (ASCE 7-22, Risk Category II), exposure, enclosure and GCpi, roof and floor live and dead loads, components and cladding pressures in psf
FBC-R R301.2; Hillsborough HC-06
- G5
Wind-borne debris protection called out where required (Vult 140 mph or more, or 130 mph within 1 mile of the coast): impact-rated openings or approved shutters
FBC-R R301.2.1.2
- G6
Florida product approval table: manufacturer, product, FL number, expiration and rated design pressure for windows, doors, garage door, roofing and shutters
Rule 61G20-3; Hillsborough HC-04
- G7
Termite protection note
FBC-R R318
- G8
Flood data: zone, base flood elevation, finished floor elevation with datum (NAVD 88), FIRM panel
FBC-R R322; local site checklists
Site
- S1
Property lines with dimensions, lot area, north arrow and scale
Local site plan checklists
- S2
Setbacks dimensioned to every structure; building height
Local zoning code
- S3
Legal description, easements and street names
Local site plan checklists
- S4
Finished floor and garage elevations, grades at the corners, drainage arrows; ground falls 6 in within 10 ft of the house
FBC-R R401.3
- S5
Driveway, walks, water and sewer or septic, A/C pad and equipment setbacks
Local site plan checklists
- S6
Protected trees near the work with barricades (Hillsborough: 5 in DBH within 30 ft; Tampa: within 20 ft)
Hillsborough LDC; City of Tampa
Architectural
- A1
Floor plan with room names, dimensions, ceiling heights, and areas (living, garage, porch, lanai)
Hillsborough HC-04
- A2
Door and window schedules with sizes, types and design pressures
FBC-R R609; local checklists
- A3
Emergency escape opening in every sleeping room: 5.7 sq ft net (5.0 at grade floor), 24 in high, 20 in wide, sill 44 in max
FBC-R R310
- A4
Egress door 32 in clear by 78 in; hallways 36 in wide
FBC-R R311.2, R311.6
- A5
At least one bathroom door with a 29 in clear opening
F.S. 553.504(2)
- A6
Smoke alarms in each sleeping room, outside sleeping areas and on each story, interconnected; photoelectric 6 ft or more from a cooking appliance; 3 ft from bath doors
From December 31, 2026: Smoke alarms in each sleeping room, outside sleeping areas, on each story and in the attached garage (or a listed heat detector there), interconnected, listed to UL 217; 10 ft or more from a cooking appliance (6 ft only where a required location needs it); 3 ft from bath doors
FBC-R R314, R314.3.1FBC-R R314.3, R314.3.1
- A7
Carbon monoxide alarms within 10 ft of each sleeping room where there is an attached garage or fuel-burning appliance
FBC-R R315; F.S. 553.885
- A8
Safety glazing marked at doors, near tubs and showers, and large low panes
FBC-R R308.4
- A9
Garage separation: no opening into a sleeping room, 1 3/8 in solid or 20 minute door, 1/2 in gypsum on the garage side
FBC-R R302.5.1, R302.6
- A10
Attic access 22 x 30 in; attic ventilation (1/150, or 1/300 with 40 to 50 percent high)
FBC-R R807.1, R806.2
- A11
Natural light and air (glazing 8 percent, openable 4 percent) or mechanical ventilation; bath exhaust to outdoors
FBC-R R303.1, R303.3
- A12
Elevations: heights from finish grade, roof slopes, materials, finish grade line, overhangs
Hillsborough HC-05
- A13
Wall sections and details: continuous load path, insulation R-values, finishes, foundation depth
Hillsborough HC-09
- A14
Roof plan: slopes, roof covering and its wind rating, high-wind underlayment method, drip edge
From December 31, 2026: Roof plan: slopes, roof covering and its wind rating, high-wind underlayment method lapped 6 in over hips and ridges, hip and ridge shingles rated (UL 2375) or set in cement, drip edge fastened 4 in on center
FBC-R R905FBC-R R905.1.1, R905.2.6.2, R905.2.8.5
Structural
- T1
Foundation plan: footing size and reinforcement, concrete strength, slab thickness, vapor retarder, footing depth
FBC-R R403, R506; Hillsborough HC-07
- T2
Masonry: filled cells and vertical bars, bond beam, lintel schedule with sizes and types
FBC-R R606, R608; Hillsborough HC-10
- T3
Roof framing: truss layout, spacing, girders, uplift connectors by maker and model, sheathing and nailing
From December 31, 2026: Roof framing: truss layout, spacing, girders, uplift connectors by maker and model, sheathing and nailing; corrosion-resistant fasteners and connectors within 3,000 ft of salt water
FBC-R R802, R803; Hillsborough HC-08FBC-R R802, R803, R332; Hillsborough HC-08
- T4
Gable end bracing where there are gables; interior bearing walls shown
Hillsborough HC-10
Electrical
- E1
Receptacle layout (kitchen counters within 24 in of an outlet, islands), GFCI and AFCI protection, service size, panel schedule and load calculation
From December 31, 2026: Receptacle layout (kitchen counters within 24 in of an outlet; island receptacles optional but then a provision for a future one, none below the top), GFCI on every kitchen receptacle, the range, dryer, dishwasher and microwave and every garage outlet except listed HVAC equipment, AFCI, tamper-resistant receptacles, surge protection rated 10 kA, service size, panel schedule and load calculation
NEC 2020 210.52, 210.8, 210.12, 220.82NEC 2023 210.52(C), 210.8(A), (D), (F), 210.12(B), 230.67, 406.12, 220.82; FBC-R E3408.1
Plumbing
- P1
Fixture layout and riser; drain sizes (no toilet on a 2 in branch); water heater location, pan and relief
FBC-R P3005, P2801
Mechanical
- M1
Equipment locations (no air handler in the attic on the prescriptive path), Manual J and S by the contractor, duct insulation, dryer vent length
From December 31, 2026: Equipment locations (no air handler in the attic on the prescriptive path), Manual J and S by the contractor, duct insulation, dryer vent length, bath fans with an automatic-off control, condensate drains in unconditioned space insulated R-3
FBC-EC R403.7.1, R403.3, R403.3.6; FBC-R M1502.4.5FBC-EC R403.7.1, R403.3, R403.3.6, R403.6.5; FBC-R M1502.4.5, M1411.9.2
Energy
- N1
Energy compliance: Form R405 or R402 referenced, climate zone 2A envelope values
From December 31, 2026: Energy compliance: Form R405-2026 (e-Ratio 0.85 or less) or Form R402-2026 with 10 credits from Table R407.2; climate zone 2A envelope values
FBC-EC R401, Table R402.1.2FBC-EC R401.2, Table R402.1.2, R405, R407