Skip to content

West Virginia

The State Fire Commission adopts two codes as legislative rules that the Legislature authorizes: the State Building Code (87CSR4: the 2018 I-codes, the 2015 IECC for houses, ASHRAE 90.1-2013 and the 2020 NEC since August 1, 2022) and the State Fire Code (87CSR1: NFPA 1 and NFPA 101, 2021 editions, current version since July 1, 2026). The building code has force only in the cities and counties that adopt it, and any local building code must be the state code; the fire code applies statewide to every building except one- and two-family dwellings, very small personal care homes and farm buildings, and is enforced, with plan review, by the State Fire Marshal. A 2026 amendment moving the building code to the 2024 I-codes, ASHRAE 90.1-2019 and the 2023 NEC is waiting for legislative authorization.

24 codes are in force here, 20 of them checked at the source, and this page was last updated November 19, 2026.

Codes in force

BuildingWest Virginia State Building Code (87CSR4): International Building Code, 2018 edition

Applies toBuildings other than one- and two-family dwellings and townhouses in the cities and counties that adopt and enforce the State Building Code; where no local code is adopted the State Fire Code still applies to these buildings. Buildings used primarily for agriculture or agritourism are exempt, with the Commissioner of Agriculture deciding eligibility. Any building code a city or county adopts must be the state code, and earlier local codes are void.

Based on, and how far it reachesIBC, 2018 edition.Each city or county chooses whether to adopt it, and which edition.

Local changesDeletes IBC 101.4.5 (fire prevention) and rewrites 113.3 so the board of appeals has five members, at least one a WV registered architect or engineer or a licensed contractor. References to the International Fire Code are replaced by the NFPA Life Safety Code, and the State Fire Code wins any conflict. A commercial structure over 7,600 square feet that needs a certificate of occupancy must be designed by a WV architect or engineer (4.3); local governments may adopt the appendices.

NextThe 2024 edition. The Fire Commission's 2026 amendment to 87CSR4 adopts the 2024 IBC (notice June 29, 2026; agency approved July 31, 2026; modified October 14, 2026 after Legislative Rule-Making Review Committee review). It still needs authorization by the Legislature; the current rule sunsets August 1, 2027.

Adopted byState Fire Commission adopts by legislative rule under W. Va. Code §15A-11-5 (formerly §29-3-5b, now repealed); cities and counties that adopt it enforce it under §8-12-13 and §7-1-3n.In force since August 1, 2022.

HousesWest Virginia State Building Code (87CSR4): International Residential Code, 2018 edition

Applies toOne- and two-family dwellings and townhouses in the cities and counties that enforce the State Building Code. Elsewhere houses have no state building permit or inspection: the State Fire Marshal has no jurisdiction over one- and two-family dwellings and the State Fire Code does not apply to them. Residential storage sheds of 200 square feet or less with no plumbing or electricity are not subject to local inspection.

Based on, and how far it reachesIRC, 2018 edition.Each city or county chooses whether to adopt it, and which edition.

Local changesChapter 11 (energy) is removed so houses follow the IECC; maximum riser 8 1/4 inches and minimum tread 9 inches; the footing clearances from slopes (R403.1.7.1, R403.1.7.2) do not apply; gas piping may be buried 12 inches deep; listing standards (UL 1995, UL/CSA 60335-2-40) are added for furnaces, heat pumps and cooling equipment. New houses over one level, with a basement, or with a fuel-burning appliance in a crawl space must protect floors with 1/2 inch gypsum board, 5/8 inch wood structural panel, 2x10 or larger joists, or sprinklers (87-4-5), and townhouses meeting R302.2 are treated the same.

NextThe 2024 edition. The 2026 amendment to 87CSR4 moves to the 2024 IRC with the same state amendments and Chapter 11 still removed; it needs authorization by the Legislature.

Adopted byState Fire Commission adopts (W. Va. Code §15A-11-5); cities and counties that adopt the State Building Code enforce it.In force since August 1, 2022.

Existing buildingsWest Virginia State Building Code (87CSR4): International Existing Building Code, 2018 edition

Applies toRepairs, alterations, additions and changes of occupancy in the cities and counties that enforce the State Building Code. For buildings under the State Fire Code, the State Fire Marshal also requires a certificate of occupancy when 50 percent or more of an existing building is renovated or reconstructed.

Based on, and how far it reachesIEBC, 2018 edition.Each city or county chooses whether to adopt it, and which edition.

Local changesReferences to the International Fire Code are replaced by the NFPA Life Safety Code (the rule cites the 2018 edition for the IEBC and the 2021 edition for the other I-codes).

NextThe 2024 edition. The 2026 amendment to 87CSR4 adopts the 2024 IEBC, substituting NFPA 1 and NFPA 101 as adopted in the State Fire Code; it needs authorization by the Legislature.

Adopted byState Fire Commission adopts; cities and counties that adopt the State Building Code enforce it.In force since August 1, 2022.

Energy, housesWest Virginia State Building Code (87CSR4): International Energy Conservation Code, 2015 edition, residential provisions

Applies toNew houses and other residential buildings in the cities and counties that enforce the State Building Code; the IRC energy chapter is removed so the IECC governs. DOE lists the code as mandatory statewide, but under W. Va. Code §15A-11-5 the State Building Code, energy provisions included, has force only where a county or city adopts it.

Based on, and how far it reachesIECC, 2015 edition.Each city or county chooses whether to adopt it, and which edition.

Local changesThe blower door limit of R402.4.1.2 is relaxed to five air changes per hour in Climate Zones 3 through 8. DOE rates the amended code as equivalent to the 2009 IECC, 6.1 percent less efficient than the model 2015 IECC; REScheck may be used.

NextThe 2024 edition. The June 2026 draft of the 87CSR4 amendment adopted the 2024 IECC with a 3 air changes per hour limit; the October 14, 2026 modified draft keeps the 2024 IECC and drops the state air leakage amendment. It needs authorization by the Legislature.

Adopted byState Fire Commission adopts (W. Va. Code §15A-11-5 requires building energy codes in the rule); cities and counties that adopt the State Building Code enforce it.In force since August 1, 2022.

Energy, other buildingsWest Virginia State Building Code (87CSR4): ANSI/ASHRAE/IESNA Standard 90.1-2013

Applies toCommercial buildings in the cities and counties that enforce the State Building Code. DOE lists the code as mandatory statewide with an effective date of September 30, 2022; the rule itself took effect August 1, 2022 and has force only where adopted locally.

Based on, and how far it reachesASHRAE 90.1, 2013 edition.Each city or county chooses whether to adopt it, and which edition.

Local changesNo amendments to the standard; the rule adds that energy benchmarking of commercial buildings is an allowable option. COMcheck may be used.

NextThe 2019 edition. The 2026 amendment to 87CSR4 adopts ASHRAE 90.1-2019 for commercial buildings; it needs authorization by the Legislature.

Adopted byState Fire Commission adopts; cities and counties that adopt the State Building Code enforce it.In force since August 1, 2022.

FireWest Virginia State Fire Code (87CSR1): NFPA 1, Fire Code, 2021 edition

Applies toEvery building statewide except one- and two-family dwellings, personal care homes for three or fewer patients and buildings used primarily for agriculture (farm buildings with group sleeping for farm workers, health care or detention uses are covered). It incorporates every publication NFPA 1 (2021) references, among them NFPA 70, which the rule amends, and standards it names such as NFPA 14, 80, 92 and 495, but excludes NFPA 5000, 472, 120 and 101A. Boilers are left to the Division of Labor, and the State Fire Code prevails over the State Building Code in a conflict.

Based on, and how far it reachesNFPA 1, 2021 edition.Applies across the state, and local governments enforce it as written.

Local changesState additions include a sprinkler and area limitation table for new buildings (2.2.1), sprinklers in fire, rescue and EMS stations begun after July 1, 2023, a high-rise package for new buildings over 75 feet, carbon monoxide alarms in new construction, NICET certification for fire protection and fire alarm companies (Level 2 to service, Level 3 to design), a ban on unvented fuel-fired heaters outside one- and two-family dwellings, and explosives and blasting rules. Projects need sealed designs and plan approval from the authority having jurisdiction before construction, and new buildings, existing industrial and storage buildings and buildings with half or more renovated need a certificate of occupancy.

Adopted byState Fire Commission adopts under W. Va. Code §15A-11-3 (this version authorized by Senate Bill 281, passed March 12, 2026, sunset August 1, 2031); the State Fire Marshal and local fire officials enforce.In force since July 1, 2026.

Life safetyWest Virginia State Fire Code (87CSR1): NFPA 101, Life Safety Code, 2021 edition, adopted in full

Applies toThe same buildings as the State Fire Code: all buildings except one- and two-family dwellings, small personal care homes and agricultural buildings. NFPA 101 is adopted in full rather than only as NFPA 1 extracts it and prevails over NFPA 1 where they conflict; the State Building Code also substitutes the Life Safety Code wherever the I-codes cite the International Fire Code.

Based on, and how far it reachesNFPA 101, 2021 edition.Applies across the state, and local governments enforce it as written.

Local changesAdds high-rise rules for new buildings over 75 feet (sprinklers and standpipes throughout, fire department voice communication, a central control station, emergency power, NFPA 92 smoke control, floor numbers in stairs), rules for classroom door locking devices (NFPA 101 15.2.2.2.4), new-building treatment of modular classrooms with a Manufacturer's Statement of Origin after January 1, 2018, and signs on sprinkler status and openable windows in residential occupancies other than houses.

Adopted byState Fire Commission adopts (W. Va. Code §15A-11-3); the State Fire Marshal and local fire officials enforce.In force since July 1, 2026.

PlumbingWest Virginia State Building Code (87CSR4): International Plumbing Code, 2018 edition

Applies toPlumbing in the cities and counties that enforce the State Building Code (the IRC plumbing chapters cover houses there). Plumbers must hold a Division of Labor license statewide (W. Va. Code chapter 21 article 14) whether or not a local code applies.

Based on, and how far it reachesIPC, 2018 edition.Each city or county chooses whether to adopt it, and which edition.

Local changesNo changes to the IPC text; where the IPC conflicts with rules of the Department of Health and Human Resources, the health rules prevail (87-4-3.2).

NextThe 2024 edition. The 2026 amendment to 87CSR4 adopts the 2024 IPC; it needs authorization by the Legislature.

Adopted byState Fire Commission adopts; cities and counties that adopt the State Building Code enforce it.In force since August 1, 2022.

MechanicalWest Virginia State Building Code (87CSR4): International Mechanical Code, 2018 edition

Applies toMechanical systems in the cities and counties that enforce the State Building Code. HVAC technicians must hold a Division of Labor certification statewide (W. Va. Code chapter 21 article 16, rule 42CSR34).

Based on, and how far it reachesIMC, 2018 edition.Each city or county chooses whether to adopt it, and which edition.

Local changesAdds listing standards for cooling towers, pool and spa heaters, furnaces, heat pumps and factory-built equipment (UL 1995, UL/CSA 60335-2-40 and 60335-2-89) and requires refrigeration systems to meet ASHRAE 15, with A2L refrigerant systems under ASHRAE 15-2019 and 34-2019.

NextThe 2024 edition. The 2026 amendment to 87CSR4 adopts the 2024 IMC with new state rules on refrigerant piping materials, refrigerant pipe shafts and shaft ventilation for A2L and other flammable refrigerants, citing ASHRAE 15-2024 and 34-2024; it needs authorization by the Legislature.

Adopted byState Fire Commission adopts; cities and counties that adopt the State Building Code enforce it.In force since August 1, 2022.

Fuel gasWest Virginia State Building Code (87CSR4): International Fuel Gas Code, 2018 edition

Applies toFuel gas piping and appliances in the cities and counties that enforce the State Building Code. For buildings under the State Fire Code, the fuel gas and LP gas standards NFPA 1 (2021) references, such as NFPA 54 and NFPA 58, come in statewide as well; their editions were not confirmed.

Based on, and how far it reachesIFGC, 2018 edition.Each city or county chooses whether to adopt it, and which edition.

Local changesUnderground gas piping must be buried at least 12 inches deep, or placed in conduit or shielded where that depth cannot be kept (IFGC 404.10, and IRC G2415.12 for houses).

NextThe 2024 edition. The 2026 amendment to 87CSR4 adopts the 2024 IFGC with the same burial depth amendment; it needs authorization by the Legislature.

Adopted byState Fire Commission adopts; cities and counties that adopt the State Building Code enforce it.In force since August 1, 2022.

ElectricalWest Virginia State Building Code (87CSR4): National Electrical Code, 2020 edition

Applies toElectrical work in the cities and counties that enforce the State Building Code. Statewide, electrical work for hire needs a State Fire Marshal license (W. Va. Code §29-3B), anyone who performs electrical inspections must hold a Fire Marshal certification (103CSR1), and the State Fire Code incorporates NFPA 70 through NFPA 1 (2021) for buildings other than houses, at an edition not confirmed.

Based on, and how far it reachesNFPA 70, 2020 edition.Each city or county chooses whether to adopt it, and which edition.

Local changesAFCI protection is not required when renovating a one- or two-family home without adding floor area, except in bedrooms, nor when floor area is added without new electrical service. The GFCI rule of 210.8(F) for HVAC equipment was deferred until January 1, 2023.

NextThe 2023 edition. The 2026 amendment to 87CSR4 adopts the 2023 NEC, keeps the AFCI renovation exception and drops the expired 210.8(F) deferral; it needs authorization by the Legislature.

Adopted byState Fire Commission adopts; cities and counties that adopt the State Building Code enforce it; the State Fire Marshal licenses electricians and certifies electrical inspectors.In force since August 1, 2022.

AccessibilityWest Virginia State Building Code (87CSR4): ICC/ANSI A117.1-2017

Applies toAccessible design of buildings under the IBC in the cities and counties that enforce the State Building Code; the federal ADA applies everywhere regardless. The 2026 amendment to 87CSR4 keeps the 2017 edition.

Based on, and how far it reachesICC A117.1, 2017 edition.Each city or county chooses whether to adopt it, and which edition.

Adopted byState Fire Commission adopts; cities and counties that adopt the State Building Code enforce it.In force since August 1, 2022.

Elevators and escalatorsElevator Safety Act rule (42CSR21): ASME A17.1-2013/CSA B44-13

Applies toElevators covered by the Elevator Safety Act (W. Va. Code §21-3C) statewide, with ASME A17.2-2014 for inspections and ASME A18.1-2014 for platform lifts and stairway chairlifts. New and modernized elevators need an acceptance inspection, and every elevator needs a certificate of operation valid 12 months, issued after inspection by a Division or private inspector holding a Division certificate of competency; safety tests are run by licensed elevator mechanics with an inspector present.

Based on, and how far it reachesASME A17.1, 2013 edition.Applies across the state, and local governments enforce it as written.

Local changesInspections have been made by approved private inspectors since 2004, with Division oversight and quality control inspections; counties and municipalities may take over inspections under work-sharing agreements.

Adopted byDivision of Labor adopts and enforces under W. Va. Code §21-3C.In force since March 30, 2018.

Pools and spasWest Virginia State Building Code (87CSR4): International Swimming Pool and Spa Code, 2018 edition

Applies toPools and spas in the cities and counties that enforce the State Building Code.

Based on, and how far it reachesISPSC, 2018 edition.Each city or county chooses whether to adopt it, and which edition.

Local changesThe state IMC amendment adds listing standards for pool and spa heaters (UL 1261, UL 1995, UL/CSA 60335-2-40, CSA C22.2 No. 236) and portable spas (UL 1563 or CSA C22.2 No. 218.1).

NextThe 2024 edition. The 2026 amendment to 87CSR4 adopts the 2024 ISPSC; it needs authorization by the Legislature.

Adopted byState Fire Commission adopts; cities and counties that adopt the State Building Code enforce it.In force since August 1, 2022.

Property maintenanceWest Virginia State Building Code (87CSR4): International Property Maintenance Code, 2018 edition

Applies toExisting buildings and premises in the cities and counties that choose it. A local government may reject the IPMC when adopting the State Building Code, or adopt the IPMC alone without the other codes; a county property maintenance code must exempt agricultural property (W. Va. Code §7-1-3n).

Based on, and how far it reachesIPMC, 2018 edition.Each city or county chooses whether to adopt it, and which edition.

NextThe 2024 edition. The 2026 amendment to 87CSR4 adopts the 2024 IPMC with the same local options; it needs authorization by the Legislature.

Adopted byState Fire Commission adopts; cities and counties that adopt it enforce it.In force since August 1, 2022.

Sprinkler rules for housesIRC Section R313 as adopted in the State Building Code (87CSR4)

Applies to87CSR4 adopts the 2018 IRC without deleting Section R313, so the house sprinkler requirement stands in the state text, but the code applies only where a city or county enforces it. Adopting cities such as Wheeling and Fayetteville delete R313 in their own ordinances (reported, not confirmed). The state rule itself lists sprinklers only as one of three ways to protect floors in new houses (87-4-5), and the State Fire Code does not reach one- and two-family dwellings.

Based on, and how far it reachesIRC R313, 2018 edition.Each city or county chooses whether to adopt it, and which edition.

Local changesNo state amendment to R313.

NextThe 2024 edition. The 2026 amendment to 87CSR4 adopts the 2024 IRC, where the sprinkler section is renumbered R309, again without deleting it; it needs authorization by the Legislature.

Adopted byState Fire Commission adopts; each city or county decides whether to enforce the code and how it amends it.In force since August 1, 2022.

Manufactured homesManufactured Housing Construction and Safety Standards Act (W. Va. Code §21-9) and board rule 42CSR19

Applies toHUD-code manufactured homes sold and installed in West Virginia. The Manufactured Housing Construction and Safety Standards Board, at the Division of Labor, is the state administrative agency for the federal standards and licenses manufacturers, dealers, distributors and contractors; its current rule took effect May 1, 2023.

Based on, and how far it reachesHUD code, current edition.Applies across the state, and local governments enforce it as written.

Local changesThe State Fire Code requires 10 feet side to side, 8 feet end to side and 6 feet end to end between manufactured homes in mobile home sites unless walls are 1-hour rated, and bars stacking homes unless designed and permitted for it. The state model floodplain ordinance calls for a licensed installer, an engineered installation design and no dry-stacked block piers in flood hazard areas.

Adopted byManufactured Housing Construction and Safety Standards Board (Division of Labor) under W. Va. Code §21-9-4 and §21-9-5.In force since May 1, 2023.

Flood rules beyond the federal minimumLocal floodplain management ordinances (NFIP) and the state model floodplain ordinance

Applies toEach county and city in the NFIP adopts and enforces its own floodplain ordinance and issues floodplain development permits; the West Virginia Emergency Management Division is the State NFIP coordinator. No statewide freeboard rule was confirmed.

Based on, and how far it reachesThe state's own code, current edition.Each city or county chooses whether to adopt it, and which edition.

Local changesThe state model ordinance presented in the Division's 2025 training raises the lowest floor, ductwork and utilities of residential and nonresidential buildings and manufactured homes to 2 feet above the base flood elevation, limits unelevated accessory structures to 300 square feet and under $7,000, and sets a flood protection setback of twice the channel width or 50 feet, whichever is less. Each local ordinance decides what actually applies.

Adopted byCounties and municipalities adopt and enforce (the model cites W. Va. Code §§7-1-3n, 7-1-3v, 7-1-3kk and 8-12-14); the Emergency Management Division coordinates.

Structural loadsASCE 7-16, through the 2018 IBC in the State Building Code

Applies toStructural loads for IBC buildings in the cities and counties that enforce the State Building Code; houses use the IRC, with climatic design values set by each local jurisdiction in IRC Table R301.2(1). No state wind, snow or frost map or table was found.

Based on, and how far it reachesASCE 7, 2016 edition.Each city or county chooses whether to adopt it, and which edition.

Local changesThe State Building Code makes IRC R403.1.7.1 and R403.1.7.2 (footing clearances from ascending and descending slopes) inapplicable, which matters on hillside lots.

NextThe 2022 edition. The 2026 amendment to 87CSR4 adopts the 2024 IBC, which references ASCE 7-22; it needs authorization by the Legislature.

Adopted byState Fire Commission adopts; cities and counties that adopt the State Building Code enforce it.In force since August 1, 2022.

Boilers and pressure vesselsHigh-Pressure Steam Boiler and Forced Flow Steam Generator Requirements (42CSR3)

Applies toHigh-pressure steam boilers (over 15 psi) and forced flow steam generators statewide: a permit to install filed at least 15 days ahead, a WV serial number, annual internal and external inspection by a Division inspector or an insurance company's special inspector, and a permit to operate. The rule leaves out pressure vessels, and the State Fire Code leaves boilers to the Division of Labor.

Based on, and how far it reachesASME BPVC and NBIC, current edition.Applies across the state, and local governments enforce it as written.

Local changesAdopts ASME BPVC Section I, parts of the National Board's NB-132 administrative rules and NBIC Parts 1 to 4 including periodic updates, so current editions apply; inspection is yearly instead of the three years in NB-132.

Adopted byDivision of Labor under W. Va. Code §21-3-7.In force since June 9, 2021.

OtherSmoke and carbon monoxide detectors (W. Va. Code §15A-10-12)

Applies toEvery one- and two-family dwelling, manufactured homes included, needs an operational smoke detector near each sleeping area, provided by the owner (a sprinkler system to the state codes may substitute). Carbon monoxide detectors, AC powered with battery backup, are required in new residential units with a fuel-burning heating or cooking source, near fuel-burning appliances in apartments, rented one- and two-family dwellings, hotels and care facilities (hardwired when newly built), and in schools and daycares with fuel-burning heat.

Based on, and how far it reachesThe state's own code, current edition.Applies across the state, and local governments enforce it as written.

Local changesViolations are misdemeanors with fines of $250, then $750, then $2,000.

Adopted bySet by statute in the State Fire Marshal article of the W. Va. Code (chapter 15A, article 10).

Checked at the source
OtherPropane gas training program certification (State Fire Code §87-1-15)

Applies toAnyone who installs or maintains liquefied petroleum gas systems must complete the Propane Education and Research Council (PERC) training program; a person working on the fuel gas system of a single-family dwelling they own or lease and occupy is exempt. NFPA 58 itself comes in through the State Fire Code's incorporation of the standards NFPA 1 (2021) references.

Based on, and how far it reachesThe state's own code, 2026.Applies across the state, and local governments enforce it as written.

Adopted byState Fire Commission adopts; State Fire Marshal enforces (W. Va. Code §15A-10-15 covers propane system installations).In force since July 1, 2026.

OtherLicensure of radon mitigators, testers, contractors and laboratories (W. Va. Code §16-34)

Applies toRadon testing and mitigation work is licensed under W. Va. Code chapter 16, article 34 (public health). The State Building Code itself does not require radon-resistant construction; IRC appendices apply only where a city or county adopts them.

Based on, and how far it reachesThe state's own code, current edition.Applies across the state, and local governments enforce it as written.

Adopted byAdministered by the director named in W. Va. Code §16-34-5; the office was not confirmed.

OtherAmusement rides and attractions; zipline and canopy tour safety (Division of Labor)

Applies toThe Division of Labor runs consumer safety programs for amusement rides and attractions and for zipline and canopy tours. The statutes, rules and standards these programs use were not confirmed.

Based on, and how far it reachesThe state's own code, current edition.Applies across the state, and local governments enforce it as written.

Adopted byWV Division of Labor.

Not yet checked at the source

Not adopted here, or not found yet

Green building and stretch codesNo green or stretch codeNo code of this kind is adopted

Applies toThe State Building Code adopts no green or stretch code, and a city or county may adopt only the state code as its building code (W. Va. Code §8-12-13, §7-1-3n). The rule names energy benchmarking of commercial buildings only as an allowable option.

Based on, and how far it reachesIgCC.

Adopted byState Fire Commission (none adopted).

Wildland-urban interfaceNo wildland-urban interface codeNo code of this kind is adopted

Applies toNeither the State Building Code nor the State Fire Code adopts a wildland-urban interface code. The State Fire Code limits outdoor burning near woodland, brush or dry fields to 5 p.m. through 7 a.m. during the forest fire seasons (March 1 to May 31 and October 1 to December 31).

Based on, and how far it reachesIWUIC.

Adopted byState Fire Commission (none adopted); forest fire season rules in 87CSR1 §87-1-8.

Modular and factory-built buildingsNo state modular or factory-built building program foundNo code of this kind is adopted

Applies toNo state approval program for modular or factory-built buildings was found. They fall under the State Building Code where a city or county enforces it and under the State Fire Code for buildings other than houses; the fire code treats modular classrooms with a Manufacturer's Statement of Origin after January 1, 2018 as new educational occupancies.

Based on, and how far it reachesThe state's own code.

Adopted byNone found; the State Fire Marshal applies the State Fire Code to modular classrooms.

Who designs, seals and builds

Architect
Practicing architecture requires registration with the West Virginia Board of Architects (W. Va. Code chapter 30 article 12). Section 30-12-12 lets others design detached single-family dwellings with their sheds and garages, multifamily residential buildings of three stories or less (basement not counted), farm buildings for no more than ten occupants, preengineered buildings, alterations that do not affect structure or safety or need no permit, and one-story commercial buildings of 7,600 square feet or less (basement not counted). The State Building Code (87CSR4 §4.3) requires a WV architect or engineer for any commercial structure over 7,600 square feet that needs a certificate of occupancy, and the State Fire Code (87CSR1 §2.1.4.b) requires sealed designs, where applicable, for the buildings it covers.W. Va. Code §30-12-12; 87CSR4 §4.3; 87CSR1 §2.1.4.bChecked at the source
Engineer
Engineers are registered by the West Virginia State Board of Registration for Professional Engineers (W. Va. Code chapter 30 article 13); the act's exemptions (§30-13-24) cover other professions, one-year permits for out-of-state engineers and supervised or in-house employees, not building types. A seal is required where the codes call for one: projects under the State Fire Code must, where applicable, be designed by a WV architect or engineer who seals the documents and gets approval from the authority having jurisdiction before construction (87CSR1 §2.1.4.b), and commercial structures over 7,600 square feet need an architect or engineer (87CSR4 §4.3). The state model floodplain ordinance also requires sealed engineering studies for floodway encroachments and fill.W. Va. Code §30-13-24; 87CSR1 §2.1.4.b; 87CSR4 §4.3Checked at the source
Contractor
The West Virginia Contractor Licensing Board licenses contractors under the WV Contractor Licensing Act (W. Va. Code chapter 30 article 42): a license is needed where the cost of the undertaking is $5,000 or more for residential work or $25,000 or more for commercial work, in classifications that include general building, general engineering, residential, multifamily, electrical, plumbing, heating ventilating and cooling, piping and specialty. Electricians (master, journeyman, specialty) are licensed by the State Fire Marshal (§29-3B), which also licenses fire protection workers (§29-3D) and home inspectors; fire protection and fire alarm companies need NICET-certified staff (87CSR1 §2.4). Plumbers (master, journeyman, plumber in training) and HVAC technicians (technician, residential technician, technician in training) are certified by the Division of Labor (§21-14, §21-16), which also licenses elevator mechanics; propane installers must complete PERC training (87CSR1 §87-1-15).W. Va. Code §30-42-3; §29-3B-2; §29-3D; §21-14; §21-16Checked at the source

Design loads and hazards

Wind
No state wind map. IBC buildings use the ASCE 7-16 wind maps through the 2018 IBC; special wind regions in West Virginia are not confirmed. IRC Table R301.2(1) entries in local ordinances: Parsons and Summersville 90 mph, Westover 115 mph.
Snow
No state snow study or table was found. Local IRC tables list 25 psf (Parsons) and 30 psf (Summersville, Westover) ground snow loads; IBC buildings use the ASCE 7-16 ground snow map, and whether parts of the eastern highlands are case study areas is not confirmed.
Seismic
No state seismic map. Local IRC tables list Seismic Design Category A (Parsons, Westover) and B (Summersville).
Frost depth
Set locally in IRC Table R301.2(1); local tables list 30 inches (Parsons, Summersville, Westover). The State Building Code makes IRC R403.1.7.1 and R403.1.7.2 (footing clearances from slopes) inapplicable.
Flood
Local floodplain ordinances under the NFIP, coordinated by the WV Emergency Management Division; the state model ordinance (2025 training) uses 2 feet of freeboard for buildings and manufactured homes, a licensed installer and engineered design for manufactured homes, and a stream setback. The WV Flood Tool shows FEMA flood zones, advisory flood heights and building-level risk.
Other hazards
Mine subsidence: every property insurance policy on a West Virginia structure includes mine subsidence coverage at a separate premium unless the insured waives it, except in 15 listed counties (among them Berkeley, Jefferson, Cabell and Wood) where it is provided only on request, with up to $200,000 reinsured by the state board and a $250 to $500 deductible (W. Va. Code §33-30-6). Smoke detectors are required in every one- and two-family dwelling and CO detectors in new residential units with fuel-burning appliances (§15A-10-12); radon testers and mitigators are licensed (§16-34). Karst, landslide and termite guidance are not confirmed.

Permits

Who issues them
Building permits come from the city or county building department where the State Building Code is enforced, such as the Charleston Building Commission, Huntington's Inspections and Permits Division, Morgantown Code Enforcement and Berkeley County's Building Permits and Inspections Department; where no local code is adopted there is no building permit for houses. For new buildings other than one- and two-family dwellings, existing industrial and storage buildings and buildings with 50 percent or more renovated, the State Fire Marshal reviews plans and must issue a certificate of occupancy (State Fire Code §2.1.4). The Division of Labor issues elevator certificates of operation and boiler permits, and local floodplain administrators issue floodplain development permits.
Review time limits
The State Fire Code (87CSR1 §2.1.4.d) gives the authority having jurisdiction 45 days from submission to complete a plan review; if the plans fall short it must list the deficiencies, the owner has 10 days to respond, and the review must then finish within 10 days. Fire marshal plan submissions are electronic only, through a portal mandatory since March 1, 2025. No state deadline for local building permit review was found.
Private review
Electrical inspectors are certified by the State Fire Marshal under 103CSR1 (Class A one- and two-family dwellings, Class B all structures, Class C plan review and all structures); each holds a master or journeyman license, a WV business license, $1 million errors and omissions and $750,000 general liability insurance. Elevator inspections have been done by approved private inspectors since 2004, and insurance companies' special inspectors inspect high-pressure boilers. Local code officials, inspectors and plans examiners must be certified under 103CSR6, and the 2026 draft of 87CSR4 recognizes contracted code officials and inspectors; no statute letting owners hire third-party building plan review was found.

Cities and counties with their own codes

  • Charleston

    Enforces the State Building Code through the Charleston Building Commission: the 2018 IBC, IRC, IEBC, IPC, IMC, IFGC and ISPSC, the 2020 NEC, the 2015 IECC and ICC A117.1-2017 from August 1, 2022, with the State Fire Code and NFPA 101 (2021) through the city fire department. The city notice says the latest edition the Legislature adopts becomes the edition in use.

  • Huntington

    The Inspections and Permits Division issues permits under city code Article 1711.05; the city lists its current codes as the 2018 IBC, 2018 IPC, 2020 NEC and NFPA 1 (2021). Contractors must also be licensed by the city and file copies of their contracts.

  • Morgantown

    The Building Inspection Division in the Code Enforcement Office issues permits to the West Virginia State Building Code, with separate applications for each trade filed through the Morgantown Access Portal. The city's pages do not state the edition in use.

  • Wheeling

    The Inspection Division issues building permits and the city's permit page links to the 2018 IBC; its codified ordinance adopts the State Building Code and deletes IRC Section R313 (house sprinklers) entirely.

  • Berkeley County

    The Building Permits and Inspections Department under the County Commission issues residential and commercial permits; commercial projects need Planning Commission approval, State Fire Marshal approval and drawings sealed by a design professional. The permit page does not name the code edition.

  • Fayetteville

    Its codified ordinance adopts the State Building Code and excludes IRC Section R313 in its entirety.

  • Summersville

    Its codified ordinance makes additions and changes to the State Building Code and sets IRC design criteria of 30 psf ground snow, 90 mph wind, Seismic Design Category B and a 30-inch frost depth to the bottom of the footing.

  • Westover

    Its codified ordinance lists IRC design criteria of 30 psf ground snow, 115 mph wind, Seismic Design Category A and a 30-inch frost depth.

  • Parsons

    Its codified ordinance lists IRC design criteria of 25 psf ground snow, 90 mph wind, Seismic Design Category A and a 30-inch frost line.

Where to read the codes, and who to ask

Not found yet

  • The 2026 amendment to 87CSR4 (2024 I-codes, ASHRAE 90.1-2019, 2023 NEC) still needs authorization by the Legislature, and no effective date has been set.
  • No current official list of the counties and cities that enforce the State Building Code was found; other sources cite a WVU land use guide counting 9 counties and 52 municipalities as of June 2015.
  • Whether a city or county that enforces the State Building Code may delete IRC R313 under W. Va. Code §8-12-13, and how many do, was not confirmed; the Wheeling and Fayetteville deletions were reported in summaries of their codified ordinances.
  • The editions of NFPA 70, NFPA 54, NFPA 58, NFPA 13 and the other standards the State Fire Code brings in through NFPA 1 (2021) were not confirmed, nor when the 2021 NFPA 1 and NFPA 101 first took effect in West Virginia.
  • Wind, snow, seismic and frost values come only from local ordinances; ASCE 7-16 special wind regions and snow case study areas in West Virginia are not confirmed.
  • Any statewide freeboard requirement (the 2025 model ordinance uses 2 feet; a 2024 association presentation lists 1 foot) and the number of participating communities were not confirmed.
  • Manufactured home installation standards in 42CSR19 were not confirmed.
  • Whether electric utilities require a certified electrical inspector's approval before connecting service was not confirmed.
  • Morgantown, Wheeling and Berkeley County pages do not name the code editions they enforce; Jefferson County, Kanawha County, Parkersburg and Martinsburg are not confirmed.
  • Licensing exemptions for plumbers (§21-14-3) and HVAC technicians (§21-16-3), the office that administers radon licensing, and the amusement ride and zipline rules were not confirmed.
  • Public pool rules of the Bureau for Public Health, storm shelter rules for schools, and karst, landslide and termite guidance are not confirmed.
  • DOE lists the commercial energy code as effective September 30, 2022, while 87CSR4 took effect August 1, 2022; the reason for the difference was not found.